ARC-HSS-9 High voltage Bus Bar heat-shrink tubing

Features/Applications : Bus Bar heat-shrink tubing is universally applied in insulated protection of Bus Bar for high-low voltage switch cabinet. Avoid short circuit fault caused by small animals such as mice, snakes and soon. Prevent Bus Bar from chemical corrosion effected by strong acid, alkali, salt, etc.Avoid accidental injure .Prevent Bus Bar from flashover, etc. Short the distance electrical pole efficiently.

Standard colors:Black, red, yellow. Other colors are available on request.

Parameter of performance

Property Typical date Test standard
Tensile strength ¡Ý10Mpa ASTM D2671
Elongation at break ¡Ý450% ASTM D2671
Tensile strength (136¡æ/168h,after aging) ¡Ý10Mpa ASTM D2671
Elongation at break(136¡æ/168h,after aging) ¡Ý400% ASTM D2671
Oxygen Index ¡Ý27 ASTM D2863
Breakdown strength ¡Ý15kV/mm ASTM D2671
Heat shock 200¡æ/4h, no dropping ASTM D2671
Flexibility under low temperature -40¡æ/4h,No crack ASTM D2671
Water absorption ¡Ü0.5% ASTM D570 A

Specification of product     Unit: mm

Goods code For 10 kV,35kV specification(mm) General Bus Bar The wall thickness for 10kV products after recovery The wall thickness for 35kV products after recovery
HSS090300A(10kV)(35kV) ¦Õ30/12 30¡Á3(4) 1.6 2.5
HSS090400A(10kV)(35kV) ¦Õ40/16 40¡Á4(5) 1.6 2.5
HSS090500A(10kV)(35kV) ¦Õ50/20 50¡Á5(6) 1.6 2.5
HSS090650A(10kV)(35kV) ¦Õ65/25 60¡Á6(8) 1.6 2.5
HSS090850A(10kV)(35kV) ¦Õ85/35 80¡Á8(10) 1.6 2.5
HSS091000A(10kV)(35kV) ¦Õ100/40 100¡Á10(12) 1.6 2.5
HSS091200A(10kV)(35kV) ¦Õ120/50 120¡Á10(12) 1.6 2.5
HSS091500A(10kV)(35kV) ¦Õ150/60   1.6 2.5
These are typical data, other specifications and type are available on request.