Heat Shrinkable Breakout Boot

Application and features:


ABR heat shrinkable breakout boot is especially designed and made from radiation Crosslinked Polyolefin ,It provide insulation and sealing the crutch place of multi-core cables at the branching point. The properties of insulating and weatherproof makes it universally applied to electric and power industry.

Material Properties:

Properties Test standard Typical data
Tensile Strength GB1040 ¡Ý12.0Mpa
Elongation at break GB1040 ¡Ý350.0%
Density GB1033 0.95¡Á103kg/m3
Hardness GB2411 ¡Ü80
Accelerated Hot aging GB14049 7 days at 136¡æ
Tensile strength variation rate GB14049 ¡Ü¡À20%
Elongation at break variation rate GB14049 ¡Ü¡À20%
Flexibility under low-temperature GB5470 No crack
Volume resistance GB1410 ¡Ý1.0¡Á1012¦¸.cm
Such are typical data,are not as a criterion for products.

ARC-ARB Heat-shrink breakout boots
Specification for 1 kV 4-core breakouts:

Type Size as supplied(mm) Size after recovery
Neck Finger Neck Finger
I.D Wall thickness Length I.D Wall thickness Length I.D Wall thickness Length I.D Wall thickness Length
46/19 45.2 2.5 110 18.8 1.15 73 18 4.4 125 5.0 2.3 77
58/26 63.4 3.0 110 26.5 1.68 69 24.5 4.5 125 6.5 3.0 75
78/33 77.2 2.7 110 33.8 1.7 75 33.5 4.5 125 9.0 3.0 77

Other specifications are available at request.
Specification for 10 kV 3-core breakouts

Type Size as supplied(mm) Size after recovery
Neck Finger Neck Finger
I.D Wall thickness Length I.D Wall thickness Length I.D Wall thickness Length I.D Wall thickness Length
56/26 56.8 2.6 115 24 1.6 69 22 4.5 125 8 3.5 70
66/30 70 2.4 115 31 1.6 72 30 4.5 125 10 3.5 73
80/38 83.5 2.6 115 38.8 1.6 72 38 4.6 125 12 4 74

10 kV 3-core breakout is classed A Class and B Class, they are the same specification. Other specifications are available at request.